194002544 - 5040OB AIR CONDITIONING SYSTEM OPERATION CHECK (PRESSURE)

Do not check the air conditioning system in the immediate vicinity of the walls (distance of approximately 2 m) in order to ensure sufficient circulation of the air by the condenser.
STEPCHECK TO BE PERFORMEDRESOLUTION IF THE CHECK IS NOT OK
1Connect the air conditioning system repressurizing station.Read the value on the high pressure gauge and compare it with the A/C pressure parameter (air conditioning), checking that the two values more or less coincideCarry out    See Test 5040BD LINEAR SENSOR OPERATION CHECK
2Check that the condenser is not blocked with dirtClean the condenser fins or repair the radiator
3Carry out    See Test 5040AB REFRIGERANT CIRCUIT CHECK