|  |  | Results of the tests | 
| 1 | AIR TEMPERATURE CHECK | All OK | Problems met | Operation | 
|---|
|  | Check
the temperature of the air at the vents  See Test   5040A  - | Continue to Step 9 | Ambient temperature at
the vents | Continue to Step  2 | 
| Temperature at the vents higher than desired | Continue to Step  3 | 
| 2 | SYSTEM PRESSURE CHECK | All OK | Problems met | Operation | 
|---|
|  | Connect
the climate control system to the repressurizing equipment and check
the system pressure  See Test   5040B  - | Continue to Step 9 | High and low pressure
values below correct figures. | Continue to Step  6 | 
| 3 | SYSTEM PRESSURE CHECK | All OK | Problems met | Operation | 
|---|
|  | Connect
the climate control system to the repressurizing equipment and check
the system pressure  See Test   5040B  - | Continue to Step 9 | High and low pressure
values below correct figures. | Repressurize the system  Op.   5040A10 | 
| High and low pressure values above correct figures. | Continue to Step  4 | 
| Low pressure value correct, but high pressure value above correct
figure (rapid compressor cycle as engine rpm increases) | Continue to Step  5 | 
| Low pressure value high and high pressure value below correct
figure | Replace the compressor  Op.   5040A20 | 
| High and low pressure vaules do not alter when the air
conditioning is activated. | Replace the compressor  Op.   5040A20 | 
| 4 | CONDENSER FAN CHECK | All OK | Problems met | Operation | 
|---|
|  | Check
that the fan cools the condenser correctly. | Continue to Step 5 | Electric fan defective | Replace the fan  Op.   5040C30 | 
| 5 | CIRCUIT LOADING CHECK | All OK | Problems met | Operation | 
|---|
|  | Check
that the system loading is not excessive. | Continue to Step 7 | System loading excessive. | Restore the correct loading  Op.   5040A10 | 
| 6 | COOLANT CIRCUIT OBSTRUCTION CHECK | All OK | Problems met | Operation | 
|---|
|  | Check
that the pipes and the filter are not obstructed. | Continue to Step 8 | Pipe obstructed | Replace the pipe | 
| Filter obstructed | Replace the filter  Op.   5040A44 | 
| 7 | CONDENSER CHECK | All OK | Problems met | Operation | 
|---|
|  | Check
that the condenser is not blocked. | Continue to Step 8 | Condenser blocked | Replace the condenser | 
| 8 | EXPANSION VALVE CHECK | All OK | Problems met | Operation | 
|---|
|  | Check
the operation of the expansion valve. | Continue to Step 9 | Expansion valve defective | Replace the expansion valve  Op.   5040B30 | 
| 9 | CHECK ON CORRECT OPERATION | All OK | Problems met | Operation | 
|---|
|  | Check
that the fault is no longer present |  | Fault persists | Search for the fault starting from another symptom' |