2398878 - L12 CLIMATE CONTROL TOO COLD

The control button operates the passenger compartment air fan normally, but the temperature of the air is not correct.
Results of the tests
0PRELIMINARY CHECKAll OKProblems metOperation
Check that the evaporator air filter is not cloggedEnd of diagnosisEvaporator air filter blockedReplace evaporator filter
1CHECKING SYSTEM PRESSUREAll OKProblems metOperation
Connect the climate control system to the repressurizing equipment and check the system pressure See Test   5040A  CHECK ON OPERATION OF AIR CONDITIONING SYSTEM (TEMPERATURE) Continue to Step 2System pressure incorrect.Restore correct system pressure.
Coolant pressure too low or too highRestore the correct coolant level
2CHECK WITH DIAGNOSTIC EQUIPMENTAll OKProblems metOperation
Connect the examiner and check for errors at the air mixing motorsContinue to Step 4Air mixing motor errorContinue to Step 3
3ELECTRICAL CIRCUIT CHECKAll OKProblems metOperation
Check the continuity/insulation of the electrical connection for the air mixing motorsContinue to Step 7Electrical conection broken or not insulated.Restore electrical connection continuity/insulation.
4CHECKING PIPES AND FILTERAll OKProblems metOperation
Check high and low pressure pipes and air conditioning system filter are not blocked.Continue to Step 5Pipes from compressor to condenser blocked.Change the pipe from compressor to condenser
Pipe from filter to expansion valve blocked.Change the pipe from filter to expansion valve
Drier filter blocked and/or damaged.Replace the filter Op. 5040A48
5CONDENSER CHECKAll OKProblems metOperation
Check that the condenser is not blocked.Continue to Step 6Condenser blockedReplace the condenser Op.   5040A40 
6EXPANSION VALVE CHECKAll OKProblems metOperation
Check that the expansion valve is working properlyContinue to Step 8Expansion valve blocked shut.Replace the expansion valve Op.   5040B30 
7CHECKING CORRECT OPERATION USING TESTERAll OKProblems metOperation
Check that the errors at the air mixing motors do not persist (after the self-learning procedure)End of diagnosisAir mixing motor errorReplace the mixed air motor
8CHECK ON CORRECT OPERATIONAll OKProblems metOperation
Check that the fault is no longer presentEnd of diagnosisFault persistsChange the climate control system node